To determine for a given sample of cement the (a) initial setting time (b) final setting time

 

OBJECT: To determine for a given sample of cement the (a) initial setting time

APPARATUS: The Vicat apparatus (IS: 5513-1969) setting time needles

Extracts from IS: 4031-1968

(i) Preparation of Test Block: Prepare a neat cement paste by gauging the cement with 0.85 times the water required to give a paste of standard consistency (P). The paste shall be gauged in the manner and under the conditions prescribed in exp. No. 1. Start a stop watch at the instant when water is added to the cement. Fill the Vicat mould, with a cement paste gauged as above, the mould resting on a non-porous plate. Fill the mould completely and smooth off the surface of the paste making it level with the top of the mould. The cement block thus prepared in the mould is the test block.

Clean appliances shall be used for gauging the temperature of water and that of test room, at the time of gauging, shall be within 27+ 2° C.

During the test, the block shall be kept at a temperature of 27+ 2° C in an atmosphere of at least 90 percent relative humidity and away from draughts. Determination of Initial Setting Time: Place the test block under the rod bearing the proper needle lower the needle gently in contact with the surface of the test block and quickly release, allowing it to penetrate into the test block. In the beginning, the needle will completely pierce the test block. Repeat this procedure until the needle, when brought in contact with the test block and released as described above, fails to pierce the block for 5±0.5 mm measured from the bottom of the mould. The period elapsing between the time when water is added to the cement and the time at which the needle fails to pierce the test block by 5+0.5mm shall be the initial setting time.

Determination of Final Setting Time: Replace the needle used for initial setting time test by the needle with an annular attachment. The cement shall be considered as finally set when, upon applying the needle gently to the surface of the test block, the needle makes an, impression thereon, while the attachment fails to do so.

The period elapsing between the time when water is added to the cement and the time at which the needle makes an impression on the surface of test block while the attachment fails to do so shall be the final setting time.

 